KXZ Refrigerant Piping

Mitsubishi KXZ equipment is manufactured to the highest standards of quality and reliability. It is imperative the method of installation and the materials used are also to high standards, to ensure trouble free operation and long term reliability.

The interconnecting pipework must be installed by a competent and trained engineer. Refrigeration quality copper tube must be used, soft copper coils or half-hard straight lenghts. The refrigation quality tube must be soft drawn seamless high grade copper pipe. The copper tube must be selected taking into account the higher operating pressures of R410A refrigerant, and that high pressures will occur throughout the system because of the reverse cycle operation. All pipework material used should be EN12735 European standard.

The supplied branch pipe kits, must be used to make connections to indoor units, and the supplied manifold kits must be used to make connections between outdoor units (where applicable); it is not permitted to use standard fittings such as elbows, tees etc. The branch pipes shall be installed in accordance with the manufacturer's instructions, allowing unrestricted flow of refrigerant, and in accordance with European standard E378:2000. All brazed joints shall be made with dry nitrogen purge to ensure the prevention of oxidisation to the internal surface of the copper pipes.

The ingress of moisture, dirt and any other contaminants to the interior of the copper pipes, and air conditioning units, must be prevented during the installation procedure. After the installation of pipework, prior to the connection of the outdoor units, and sealing of insulation joints, the pipework must be pressure tested for leakage, using dry nitrogen.

Additional Refrigerant

Additional R410A refrigerant only shall be used, and must be charged by weight only, using electronic scales. The amount of additional refrigerant must be accurately calculated from the manufactureris data, based on the length and diameter of each section of the liquid refrigerant pipework of the system.

Single outdoor unit piping examples:

kx6-bakır-borulama

Combination outdoor unit piping examples

mitsubishi-heavy-vrf-sistemleri-bakır-borulama-örneği
Outdoor Units Main pipe size (normal) Pipe size for an actual length of 90m or longer
Gas pipe Liquid pipi Gas pipe Liquid pipe
280 ø22.22 t 1.0 ø9.52 t 0.8 ø25.4 (ø22.22) t 1.0 ø12.7 t 0.8
335 ø25.4 (ø22.22) t 1.0 ø12.7 t 0.8
400 ø25.4 (ø28.58) t 1.0 ø28.58 t 1.0
450 ø28.58 t 1.0 ø31.8 t 1.1
(ø28.58 t 1.0)
475 ø15.88 t 1.0
500
560
615
670
735 ø31.8 t 1.1
(ø34.92 t 1.2)
ø15.88 t 1.0 ø38.1 t 1.35
(ø34.92 t 1.2)
ø19.05 t 1.0
800
850
900
950
1000 ø38.1 t 1.35
(ø34.92 t 1.2)
1060 ø19.05 t 1.0 ø22.22 t 1.0
1120
1200
1250
1300
1350
1425
1450
1500
1560
1620
1680
mm inch
ø9.52 3/8"
ø12.7 1/2"
ø15.88 5/8"
ø19.05 3/4"
ø22.22 7/8"
ø25.4 1"

mm inch
ø28.58 11/8"
ø31.8 11/4"
ø34.92 13/8"
ø38.1 11/2"
ø44.5 13/4"
ø50.8 2"

 

Branch Piping Set Headet Set
mitsubishi-heavy-vrf-sistemleri-joint
DIS-22-1G / DIS-180-1G
mitsubishi-heavy-vrf-sistemleri-kxv
HEAD6-180-1G
mitsubishi-heavy-vrf-sistemleri-joint
DIS-371-1G / DIS-540-3
mitsubishi-heavy-vrf-sistemleri-kxv-branşman-kiti
DOS-2A-3
DOS-3A-3

Outdoor Unit Branch Piping Set
For two units(615~1120) DOS-2A-3
For three units (1200~1680) DOS-3A-3

Toplam Capacity of indoor units Branch piping set Header set
Model Branches
~179 DIS-22-1G HEAD4-22-1G Max 4 branches
180~370 DIS-180-1G HEAD6-180-1G Max 6 branches
371~539 DIS-371-1G HEAD8-371-2 Max 8 branches
540~ DIS-540-3 HEAD8-540-3 Max 8 branches