KXZ Outdoor Unit Heat Pump System 50-52-54-56-58-60 HP |
VRF Products» KXZ Outdoor Unit Heat Pump System 50-52-54-56-58-60 HP |
- KXZ heat pump 2-pipe system offers high performance for VRF applications that require only heating or cooling; Ideal for wide application areas.
- Connections up to 130% capacity and 80 indoor units.
- Thanks to high efficiency, EER values up to 3.65
- In KXZ, only DC inverter compressor is available.
- KXZ presents 160 m maximum pipe length and up to 1000 m total piping, which are the leading limits of the industry.
|
 |
|
Model |
FDC1425KXZE1 |
FDC1450KXZE1 |
FDC1500KXZE1 |
FDC1560KXZE1 |
FDC1620KXZE1 |
FDC1680KXZE1 |
Combination (FDC) |
475KXZE1 |
475KXZE1 |
500KXZE1 |
500KXZE1 |
500KXZE1 |
560KXZE1 |
475KXZE1 |
475KXZE1 |
500KXZE1 |
500KXZE1 |
560KXZE1 |
560KXZE1 |
475KXZE1 |
500KXZE1 |
500KXZE1 |
560KXZE1 |
560KXZE1 |
560KXZE1 |
Nominal Horse Power |
50HP |
52HP |
54HP |
56HP |
58HP |
60HP |
Power Source |
3 Phase 380-415V, 50Hz |
Nominal Capacity |
Cooling |
kW |
142.5 |
145.0 |
150.0 |
156.0 |
162.0 |
168.0 |
Heating |
159.0 |
162.0 |
168.0 |
175.0 |
182.0 |
189.0 |
Electrical Charecteristics |
Starting Current |
A |
24 |
Power Consumption |
Cooling |
kW |
41.94 |
41.93 |
41.91 |
44.56 |
47.21 |
49.86 |
Heating |
39.00 |
39.49 |
40.47 |
42.93 |
45.39 |
47.85 |
Running Current |
Cooling |
A |
67.8 |
67.8 |
67.8 |
72.1 |
76.4 |
80.7 |
Heating |
63.0 |
63.8 |
65.4 |
69.4 |
73.4 |
77.4 |
Exterior Dimensions |
HxWxD |
mm |
2048x4050x720 |
Net Weight |
|
kg |
1110 |
Refrigerant Charge |
R410A |
kg |
11.5x3 |
Refrigerant Piping Size |
Liquid Line |
mm/in |
ø19.05(3/4") |
Gas Line |
ø38.1 (1 1/2") [34.92(1 3/8")] |
Capacity Connection |
% |
50~130 |
Number of Connectable Indoor Units |
|
80 |
|
 |