KXZ Outdoor Unit Heat Pump System 14-16-17-18-20 HP |
VRF Products» KXZ Outdoor Unit Heat Pump System 14-16-17-18-20 HP |
- KXZ heat pump 2-pipe system offers high performance for VRF applications that require only heating or cooling; Ideal for wide application areas.
- Connections up to 130% capacity and 48 indoor units.
- Thanks to high efficiency, EER values up to 3.6
- In KXZ, only DC inverter compressor is available.
- KXZ presents 160 m maximum pipe length and up to 1000 m total piping, which are the leading limits of the industry.
|
 |
|
Model |
FDC400KXZE1 |
FDC450KXZE1 |
FDC475KXZE1 |
FDC500KXZE1 |
FDC560KXZE1 |
Nominal Horse Power |
|
|
14HP |
16HP |
17HP |
18HP |
20HP |
Power Source |
|
|
3 Phase 380-415V, 50Hz |
Nominal Capacity |
Cooling |
kW |
40.0 |
45.0 |
47.5 |
50.0 |
56.0 |
Heating |
45.0 |
50.0 |
53.0 |
56.0 |
63.0 |
Electrical characteristics |
Starting Current |
A |
8 |
Power Consumption |
Cooling |
kW |
10.96 |
13.98 |
13.98 |
13.97 |
16.62 |
Heating |
10.69 |
12.50 |
13.00 |
13.49 |
15.95 |
Running Current |
Cooling |
A |
17.5 |
22.4 |
22.6 |
22.6 |
26.9 |
Heating |
17.5 |
20.4 |
21.0 |
21.8 |
25.8 |
Exterior dimensions |
HxWxD |
mm |
2048x1350x720 |
Net Weight |
|
kg |
317 |
370 |
Refrigerant Charge |
R410A |
kg |
11.5 |
Sound Pressure Level |
Cooling / Heating |
dB(A) |
60/62 |
61/62 |
61/61 |
61/62 |
64/66 |
Refrigerant Piping Size |
Liquid Line |
mm/in |
ø12.7(1/2") |
Gas Line |
ø25.4(1") [ø28.58(1 1/8")] |
ø28.58(1 1/8") |
Capacity Connection |
% |
50~130 |
Number of Connectable Indoor Units |
|
34 |
39 |
41 |
43 |
48 |
|
 |