KXZ Outdoor Unit Heat Pump System 10-12 HP

  • KXZ heat pump 2-pipe system offers high performance for VRF applications that require only heating or cooling; Ideal for wide application areas.
  • Connections up to 130% capacity and 29 indoor units.
  • Thanks to high efficiency, COP values up to 4.33
  • In KXZ, only DC inverter compressor is available.
  • KXZ presents 160 m maximum pipe length and up to 1000 m total piping, which are the leading limits of the industry.
mitsubishi-heavy-vrf-sistemleri-kx6-dış-üniteler
For more information about the product
We'll Call You
Model FDC280KXZE1 FDC335KXZE1
Nominal Horse Power     10HP 12HP
Power Source     3 Phase 380-415V, 50Hz
Nominal Capacity Cooling kW 28.0 33.5
Heating 31.5 37.5
Electrical characteristics Starting Current A 8
Power Consumption Cooling kW 7.24 8.96
Heating 7.28 9.04
Running Current Cooling A 11.9 14.6
Heating 12.0 14.8
Exterior dimensions HxWxD mm 1690x1350x720
Net Weight   kg 272
Refrigerant Charge R410A kg 11.0
Sound Pressure Level Cooling / Heating dB(A) 55/57 61/58
Refrigerant Piping Size Liquid Line mm/in ø9.52(3/8") ø12.7(1/2")
Gas Line ø22.22(7/8") ø25.4(1") [ø22.22(7/8")]
Capacity Connection % 50~130
Number of Connectable Indoor Units   24 29