KXR6 Outdoor Unit Heat Recovery System 26-28-30-32 HP

  • KXR6 3-pipe heat recovery system is a VRF system suitable for almost all building types, requiring simultaneous heating and cooling. Energy efficiency is maximized via DC inverter compressor use. KXR6, with its 3.3 up to 3.5 COP (cooling) value, is used where heating plus cooling is needed.
  • Indoor unit connection potential ranging from 50% up to 160% capacity.
  • KXR6 presents 160 m critical line length and up to 1000 m total piping, which are the leading limits of the industry.
mitsubishi-heavy-vrf-sistemleri-kx6-dış-üniteler
For more information about the product
We'll Call You
Model FDC735KXRE6 FDC800KXRE6 FDC850KXRE6 FDC900KXRE6
Combination (FDC)   335KXRE6-K 400KXRE6 400KXRE6 450KXRE6
  400KXRE6 400KXRE6 450KXRE6 450KXRE6
Nominal Horse Power   26HP 28HP 30HP 32HP
Power Source     3 Faz 380-415V, 50Hz
Nominal Capacity Cooling kW 73.5 80.0 85.0 90.0
Heating 82.5 90.0 95.0 100.0
Electrical Charecteristics Starting Current A 16
Power Consumption Cooling kW 21.08 23.22 25.10 26.98
Heating 21.3 23.86 25.25 26.64
Running Current Cooling kW 34.4 - 31.5 38.0 - 34.8 40.6 - 37.2 43.2 - 39.6
Heating 35.4 - 32.4 39.8 - 36.4 41.9 - 38.3 44.0 - 40.2
Exterior Dimensions HxWxD mm 1690x2700x720
Net Weight   kg 674
Refrigerant Charge R410A kg 33
Refrigerant Piping Size Liquid Line mm/in ø15.88 (5/8")
Suction Gas Line ø31.75 (1 1/4") [ø34.92 (1 1/8")]
Discharge Gas Line ø25.4 (1") [ø28.58 (1 1/8")] ø28.58 (1 1/8")
Capacity Connection   % 50 - 160
Number of Connactable Indoor Units     53 58 61 65