KXR6 Outdoor Unit Heat Recovery System 18-20-22-24 HP

  • KXR6 3-pipe heat recovery system is a VRF system suitable for almost all building types, requiring simultaneous heating and cooling. Energy efficiency is maximized via DC inverter compressor use. KXR6, with its 2.6 up to 3.3 COP (cooling) value, is used where heating plus cooling is needed.
  • Indoor unit connection potential ranging from 50% up to 160% capacity
  • KXR6 presents 160 m critical line length and up to 1000 m total piping, which are the leading limits of the industry.
mitsubishi-heavy-vrf-sistemleri-kx6-dış-üniteler
For more information about the product
We'll Call You
Model FDC504KXRE6 FDC560KXRE6 FDC615KXRE6 FDC680KXRE6
Nominal Horse Power   18HP 20HP 22HP 24HP
Power Source     3 Faz 380-415V, 50Hz
Nominal Capacity Cooling kW 50.4 56.0 61.0 68.0
Heating 56.5 63.0 69.0 73.0
Electrical Charecteristics Starting Current A 8
Power Consumption Cooling kW 15.18 17.95 21.47 25.99
Heating 15.12 16.79 19.11 19.69
Running Current Cooling kW 23.8 - 21.8 28.4 - 26.0 34.7 - 31.8 44.9 - 41.1
Heating 25.2 - 23.1 28.0 - 25.7 31.6 - 28.9 34.0 - 31.1
Exterior Dimensions HxWxD mm 2048x1350x720
Net Weight   kg 361 375
Refrigerant Charge R410A kg 11.5 11.5
Sound Pressure Level Cooling / Heating dB(A) 62/62 63.5/63.5 64/64.5 65.5/65.5
Refrigerant Piping Size Liquid Line mm/in ø12.7 (1/2")
Suction Gas Line ø28.58 (1 1/8")
Discharge Gas Line ø22.22 (7/8") ø25.4 (1") [ø22.22 (7/8")]
Capacity Connection   % 50 - 160
Number of Connactable Indoor Units     36 40 44 49